Overview:
HT-100CT Series is a Capacitance Type Level Transmitter which continuously
measures liquid levels using of liquid's dielectric constant.It can be easily installed
and adjusted,and can be easily applied to corrosive liquids and widely used in
general industries,chemical and oil plants.
Characteristics:
Widely used to measure various liquid levels
Strong structure and semi-permanent life cycle due to moveless part
Various probe types for wide application
Easyinstallation of wire type(HT-100CTW/HT-100CTW-2)
Applicable to corrosive liquid
Interface measurement between water and oil is available
Applicabletoexplosion area(HPC-100CT/HPC-100CT-2)
NAMURNE43is applied.
Operation Principle:
When there are two conductors insulated each other,the value of capacitance formed
between two conductors is a function ofthe sizes of two conductors,relative location
of two conductors and the dielectric constant of material placed between two
conductors.Underthe conduction that airof dielectric constant e1 exists in the space
between two concentric conductors.Iower part of space between two conductors
is filled with material of dielectric constant e2 as shown below,the change of
capacitance is expressed as follows:
Since is a constant value as an initial condition.and getthisvalue as K.△C
becomes a function of level of material only.Therefore,level can be obtained through
the measurement of △C.